Stack Height of Diesel Generator Sets |
|
For
Generator Sets |
Total Height of stack in
Metre |
|
50
KVA |
Ht. of the building + 1.5 metre |
|
50-100
KVA |
Ht. of the building + 2.0 metre |
|
100-150
KVA |
Ht. of the building +2.5 metre |
|
150-200
KVA |
Ht. of the building + 3.0 metre |
|
200-250
KVA |
Ht. of the building + 3.5 metre |
|
250-300
KVA |
Ht. of the building + 3.5 metre |
|
|
|
|
Source :
Environmental Standards for Ambient Air, Automobiles, |
Fuels, Industries and Noise, Central
Pollution Control Board, |
|
Ministry of Environment
& Forest. |
|
|
|
|